European Style Prefabricated Box Type Substation IP33 Protection For Power Distribution
Product Details:
| Place of Origin: | Zhuhai, China |
| Brand Name: | Dong Sheng Yuan |
| Model Number: | YBM-12/0.4 |
Payment & Shipping Terms:
| Delivery Time: | T+30 |
|---|---|
| Payment Terms: | TT |
|
Detail Information |
|||
| Usage: | Power,Distribution | Rated Frequency: | 50Hz,50/60Hz |
|---|---|---|---|
| Insulation Level: | High | Application: | Power |
| Rated Voltage: | 12kV | ||
| Highlight: | IP33 Protection Box Type Substation,Power Distribution Prefabricated Substation,European Style Box Type Substation |
||
Product Description
European-style Box-type Substation (YBM-12/0.4 Prefabricated Substation)
The YBM-12/0.4 prefabricated substation, also known as European style modular substation, is a compact power distribution solution integrating high voltage components, power transformer, and low voltage components. It features high combination flexibility, compact size, mobility, reliable operation, easy maintenance, and aesthetic design.
Product Introduction
This innovative electrical power distribution substation is widely applicable in urban public distribution networks, high-rise buildings, residential areas, mining operations, ports, oil fields, parks, car stations, airports, subways, and highways.
Performance Features
- Excellent thermal insulation with double-layer cabinet structure and interlayer insulation material, effectively reducing temperature rise from sunlight
- Safe and reliable operation with XGN15-12 or SRM-12 high voltage switchgear, featuring Five-Preventions interlock and waterproof door frames
- Convenient maintenance with automatic lighting in each compartment and transformer track/cart system for easy installation and replacement
- Durable construction using marine-grade zinc-rich epoxy primer and epoxy anticorrosive mortar, with customizable colors and galvanized electrical components
Technical Parameters
| Items | Unit | Parameter |
|---|---|---|
| High-Voltage Components | ||
| Rated Frequency | Hz | 50/60 |
| Rated Voltage | kV | 12 |
| Withstand Voltage of Working Frequency | kV | 42 |
| Withstand Voltage of Thunder Impact | kV | 75 |
| Rated Current | A | 630 |
| Rated Instantaneous Withstand Current | kA | 20(2S) |
| Rated Peak Withstand Current | kA | 50 |
| Low-Voltage Components | ||
| Rated Voltage | V | 400 |
| Rated Current of Main Circuit | A | 100-4000 |
| Rated Instantaneous Withstand Current | kA | 50 |
| Rated Peak Withstand Current | kA | 105 |
| Transformer | ||
| Rated Capacity | kVA | 50-2000 |
| Tap Range | ±2*2.5% or±5% | |
| Linked Groups | D,yn11 | |
| Noise Level | dB | ≤55 |
| Shell Protection Grades | IP33 | |
Applicable Conditions
- Temperature range: -25°C to +40°C
- Altitude: ≤1000m (up to 3000m with special transformer and components)
- Vertical gradient: ≤5°
- Workplaces must be free of violent vibration, conductive dust, explosive hazards, and corrosive elements
- Air humidity: ≤90% at +25°C
- Outdoor wind speed: ≤35m/s
Schematic Diagram of Structure
Installation
The manufacturer provides foundation layout specifications. Lightning conductors must be pre-laid in or around the foundation. Grounding requires at least two cables with resistance ≤4Ω. The substation-foundation gap must be sealed with cement concrete for waterproofing.
Ordering Instructions
Required information from customer:
- Product model
- Operation conditions
- Transformer model and capacity
- Cable installation solution and component specifications
- Shell color code
- Any additional requirements
Want to Know more details about this product