Product Details:
|
Rating Voltage: | 12/24/36KV | Rating Current: | 630A 1250A |
---|---|---|---|
Rating Frequency: | 50Hz | Standerds: | GB ISO |
OEM/ODM: | Available | ||
High Light: | Medium Voltage Gas Insulated Switchgear,36KV Medium Voltage Gas Insulated Switchgear,HXGN15 mv gis switchgear |
Gas Insulated SF6 Switchgear HXGN15 series Swg 12/24/36KV 630A 1250A MV switch panel GB ISO
Product Introduction
General
HXGN15 series unit type SF6 ring net cabinet with SF6 load switch as the main switch, for the whole cabinet, is suitable for electric distribution automation and compact also expandable metal close switchgear. It characters by its simple structure, flexible operation, reliable interlocking and convenient installation, etc., which can provide satisfactory technical projects both for different application occasions and users. With the adoption of sensor technology and the protection relay up to date, plus the advanced technology and flexible assembly project, HXGN15 unit type SF6 ring net cabinet can completely meet the requirement of a continuously variable market. It can take self-produced FLBS36 SF6 load break switch; also according to user’s demand can be assembled with the internationally top-ranking VB4 series vacuum circuit breaker with a permanent magnetic mechanism made by AREVA or HD4 type SF6 circuit breaker made by AREVA or HD4 type SF6 circuit breaker made by ABB or with our VS1-12 type vacuum circuit breaker with the permanent magnetic mechanism. Operational methods for the main switch inside the ring main unit can be either manual or electric power-driven. And It can meet the requirement of “Four Controls” when matched with FTU and RTU.
Feature
1. Metal-clad and fully enclosed structure, can prevent dirt and small animals from the entrance.
2. Through the observation windows in the door panel switch position and general condition can be clearly viewed.
3. The door and switch operating handle is mechanically interlocked to ensure the door cannot be opened with the switch closed and the switch cannot be closed with the door open.
4. The switchgear use vacuum switches combined with solid insulation material. This environmentally-friendly technology avoids the use of SF6 as an insulation gas.
5. Reliable FIVE-PREVENTION interlock can effectively prevent mal-operation.
Service Environment
1. Air temperature: -35℃~+40℃
2. Humidity: Monthly average humidity 95%; Daily average humidity 90%.
3. Altitude:≤ 2500m
4. Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
5. No frequent violent shake
Technical Data
No. | Item | Unit | Parameter | |||
1 | Rated voltage | kV | 12 | 24 | 36 | |
2 | Rated frequency | Hz | 50/60 | |||
3 | Rated current | A | 630(1250*) | |||
4 |
1min Power frequency withstand voltage |
wet | kV | 38 | 50 | 70 |
dry | kV | 48 | 60 | 85 | ||
5 | Lightning impulse withstand voltage | kV | 75 | 125/150 | 170 | |
6 | Rated short circuit breaking current (peak) | kA | 80 | 63 | 63 | |
7 | Rated active load and close circuit breaking current | A | 63 | 50 | 50 | |
8 | Rated transferring current | A | 1700 | 1200 | 1200 | |
9 | Rated short circuit making a current (peak) | kA | 80 | 63 | 63 | |
10 | Rated cable(line) charging breaking current | A |
50 and 10 50/10 |
|||
11 | Cable charge breaking current in earthing fault | A | 20 | 20 | 20 | |
12 | Rated withstand current (peak) | kA | 80 | 63 | 63 | |
13 | Short-time withstand current (2s) | kA | 25 | 20 | 20 | |
14 | Mechanism life | times | 5000 | 2000 | 2000 |
Note: For short circuit breaking and the peak current is based on Fuse plus combination
Contact Person: Ken Chan (English)
Tel: 0086 13938551009