Product Details:
Place of Origin: China
Brand Name: KNKONG
Certification: CB,ISO,IEC
Model Number: VS1-12
Payment & Shipping Terms:
Minimum Order Quantity: 1
Packaging Details: Standard export packaging
Delivery Time: 15 working days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 1000 Unit per month

310 Phase Spacing Fixed 12KV Circuit Breaker Modularized Mechanism

Description
Voltage: 12KV Current: 630-2000A
Breaking Current: 20-25KA Type: Fixed
Phase Spacing: 310 Manufactory: KNKONG
High Light:

Fixed 12KV Circuit Breaker

,

310 Phase Spacing Circuit Breaker

,

Modularized Mechanism 12KV Circuit Breaker

310 Phase Spacing Fixed 12KV Circuit Breaker Modularized Mechanism

 

Voltage: 12KV

Current: 630-2000A

Breaking current: 20KA

Type: Fixed

Phase spacing: 310

 

Product overview

The VS1 series circuit breaker is completely independently developed by Knkong based on advanced design concepts; it adopts a modular mechanism for easy installation, maintenance, testing, and operation. Compared with the traditional VS1 circuit breaker. It has higher operational stability, higher safety, and longer service life. This product can meet the application needs of customers in 12kV and 24kV power transmission and distribution systems and is widely used in electric power, energy, petrochemical, metallurgy, manufacturing, transportation, construction, environmental protection, and other industries, as well as large enterprises and national key projects

 

VS1-Series circuit breaker features high stability and high reliability

The mechanism of VS1 series vacuum circuit breakers has been specially optimized for transmission components. The modular spring mechanism has the advantages of convenient maintenance, short maintenance time after a power failure, and strong versatility of parts. It has good compatibility with the vacuum interrupter, greatly improves the technical parameters, and has more excellent performance.

 

Technical Parameters

No. Item Unit Parameter
1 Rated voltage KV 12
2 Rated frequency Hz 50/60
3

 

Rated insulation level

1min power frequency withstand voltage(r. m. s)

 

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)

 

 

4

 

 

Rated current

 

 

A

630 630 1250 1600
1250 1250 1600 2000
    2000 2500
    2500 3150
      4000
5 Rated short-circuit breaking current

 

KA

20 25 31.5 40
6 Rated short-time withstand current 20 25 31.5 40
7 Rated short-circuit marking current 50 63 80 100
8 Rated peak withstand current 50 63 80 100
9 Rated duration of short-circuit     s 4
10 Rated operating sequence   O-0.3s-O/C-180s-O/C
11 Breaking times of rated short-circuit current Times 30/20 times(40KA)
12 Mechanical endurance Ops 20000
13 Rated single capacitor bank breaking current

 

A

630
14 Rated back-to-back capacitor bank breaking current 400
15 Double-earth fault breaking current 27.4
16 Allowable maximum contact erosion

 

mm

3
17 Clearance between open contacts 10±1
18 Over stroke 3.5±0.5
19 Non-simultaneity of 3-phase opening and closing

ms

 

≤2
20 Bounce duration of contact closing ≤2
21 Average breaking speed (instant breaking 6mm)

m/s

 

1.1±0.2
22 Average making speed 0.8±0.2
23 Making time

ms

 

≤100
24 Breaking time ≤50

 

 

25

 

Resistance of each phase main circuit

 

μ Ω

630A ≤50
1250A ≤45
1600A~2000A ≤35
≥2500A ≤25
26 Contact breaking bounce amplitude mm ≤2

 

27

Rated operating voltage Rated operating voltage(V)AC/DC

 

V

24* 110 220
Scope of normal operation voltage Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28 Rated voltage of energy storage motor V AC110/220,DC110/220
29 Energy storage time S ≤15

 

 

 

 