Product Details:
|
Using Voltage: | 12-24KV | Running Current: | 630A 1250A 2000A |
---|---|---|---|
Breaking Capacity: | Max 20KA | Type: | Withdrawable |
Original: | China | Manufactory: | KNKONG-ELECTRIC |
Highlight: | Withdrawable Modular VCB Circuit Breaker,20KA Breaking VCB Circuit Breaker,ISO VCB Circuit Breaker |
20KA Breaking alternating withdrawable solid-sealed pole VCB 12KV VS1 series
Voltage: 12-24 KV
Current: 630-1250A-2000A
Breaking current: max 20KA
Type: withdrawable
Product overview
Secondary circuit
The secondary control circuit board of Knkong-electric's VS1 series vacuum circuit breaker uses a modular design. The electrical connection of the machine uses high-grade self-buckle plugs, which are convenient for replacement and ensures reliable operation of the electrical connection.
High-performance oil buffer
The high-performance breaking buffer can significantly reduce the amplitude of overshoot and spring back generated by the moving contact of the VS1 vacuum circuit breaker during breaking, and avoid the overshoot of the moving contact leading to partial fatigue of the vacuum interrupter bellows Loss of mechanical durability. With the decrease of the rebound amplitude of the moving contact, the reignition phenomenon has not been found in the test of the switched capacitor bank.
Technical Parameters
No. | Item | Unit | Parameter | ||||||
1 | Rated voltage | KV | 12 | ||||||
2 | Rated frequency | Hz | 50/60 | ||||||
3 |
Rated insulation level |
1min power frequency withstand voltage(r. m. s) |
KV |
42(phase-to-phase, phase-to-earth) 48(across the isolating distance) |
|||||
Lighting impulse withstand voltage (peak) |
75(phase-to-phase, phase-to-earth) 85(across the isolating distance) |
||||||||
4 |
Rated current |
A |
630 | 630 | 1250 | 1600 | |||
1250 | 1250 | 1600 | 2000 | ||||||
2000 | 2500 | ||||||||
2500 | 3150 | ||||||||
4000 | |||||||||
5 | Rated short-circuit breaking current |
KA |
20 | 25 | 31.5 | 40 | |||
6 | Rated short-time withstand current | 20 | 25 | 31.5 | 40 | ||||
7 | Rated short-circuit marking current | 50 | 63 | 80 | 100 | ||||
8 | Rated peak withstand current | 50 | 63 | 80 | 100 | ||||
9 | Rated duration of short-circuit | s | 4 | ||||||
10 | Rated operating sequence | O-0.3s-O/C-180s-O/C | |||||||
11 | Breaking times of rated short-circuit current | Times | 30/20 times(40KA) | ||||||
12 | Mechanical endurance | Ops | 20000 | ||||||
13 | Rated single capacitor bank breaking current |
A |
630 | ||||||
14 | Rated back-to-back capacitor bank breaking current | 400 | |||||||
15 | Double-earth fault breaking current | 27.4 | |||||||
16 | Allowable maximum contact erosion |
mm |
3 | ||||||
17 | Clearance between open contacts | 10±1 | |||||||
18 | Over stroke | 3.5±0.5 | |||||||
19 | Non-simultaneity of 3-phase opening and closing |
ms
|
≤2 | ||||||
20 | Bounce duration of contact closing | ≤2 | |||||||
21 | Average breaking speed (instant breaking 6mm) |
m/s
|
1.1±0.2 | ||||||
22 | Average making speed | 0.8±0.2 | |||||||
23 | Making time |
ms
|
≤100 | ||||||
24 | Breaking time | ≤50 | |||||||
25 |
Resistance of each phase main circuit |
μ Ω |
630A | ≤50 | |||||
1250A | ≤45 | ||||||||
1600A~2000A | ≤35 | ||||||||
≥2500A | ≤25 | ||||||||
26 | Contact breaking bounce amplitude | mm | ≤2 | ||||||
27 |
Rated operating voltage | Rated operating voltage(V)AC/DC |
V |
24* | 110 | 220 | |||
Scope of normal operation voltage | Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed | ||||||||
28 | Rated voltage of energy storage motor | V | AC110/220,DC110/220 | ||||||
29 | Energy storage time | S | ≤15 |