Product Details:
|
Voltage: | 12KV | Current: | 1250A |
---|---|---|---|
Breaking Current: | 25KA | Type: | Withdrawable |
Original: | China | Manufactory: | KNKONG |
High Light: | VS1 Series Vacuum Circuit Breaker,Embedded Pole Vacuum Circuit Breaker,Modular VCB Vacuum Circuit Breaker |
VCB 12KV 1250A VS1 Series Vacuum Circuit Breaker
Voltage: 12KV
Current: 1250A
Breaking current: 25KA
Type: withdrawable
Product overview
VS1-Series embedded pole. vacuum circuit breakers are applicable to 12kV, three-phase AC 50Hz indoor switchgear and can serve as protection and control units for industrial and mining establishment transformer substation equipment. With modular and independent-frame design for their spring operating mechanisms, VS1-Series circuit breakers can operate with KYN28-12(24) mid-set and fixed switchgear. These circuit breakers are subject to both fixed installation and assembly with the truck as a handcart unit
Applicable standards
1EC62271-100 High-voltage switchgear and control-gear-Part 100: Alternating-current circuit-breakers
Secondary circuit
VS1-Series vacuum circuit breakers adopt modular designs for their secondary control circuit boards. The electric connection of the mechanisms employs high-grade self-fastener plugs, which both facilitates replacement and ensures reliable electrical connection
Technical Parameters
No. | Item | Unit | Parameter | ||||||
1 | Rated voltage | KV | 12 | ||||||
2 | Rated frequency | Hz | 50/60 | ||||||
3 |
Rated insulation level |
1min power frequency withstand voltage(r. m. s) |
KV |
42(phase-to-phase, phase-to-earth) 48(across the isolating distance) |
|||||
Lighting impulse withstand voltage (peak) |
75(phase-to-phase, phase-to-earth) 85(across the isolating distance) |
||||||||
4 |
Rated current |
A |
630 | 630 | 1250 | 1600 | |||
1250 | 1250 | 1600 | 2000 | ||||||
2000 | 2500 | ||||||||
2500 | 3150 | ||||||||
4000 | |||||||||
5 | Rated short-circuit breaking current |
KA |
20 | 25 | 31.5 | 40 | |||
6 | Rated short-time withstand current | 20 | 25 | 31.5 | 40 | ||||
7 | Rated short-circuit marking current | 50 | 63 | 80 | 100 | ||||
8 | Rated peak withstand current | 50 | 63 | 80 | 100 | ||||
9 | Rated duration of short-circuit | s | 4 | ||||||
10 | Rated operating sequence | O-0.3s-O/C-180s-O/C | |||||||
11 | Breaking times of rated short-circuit current | Times | 30/20 times(40KA) | ||||||
12 | Mechanical endurance | Ops | 20000 | ||||||
13 | Rated single capacitor bank breaking current |
A |
630 | ||||||
14 | Rated back-to-back capacitor bank breaking current | 400 | |||||||
15 | Double-earth fault breaking current | 27.4 | |||||||
16 | Allowable maximum contact erosion |
mm |
3 | ||||||
17 | Clearance between open contacts | 10±1 | |||||||
18 | Over stroke | 3.5±0.5 | |||||||
19 | Non-simultaneity of 3-phase opening and closing |
ms
|
≤2 | ||||||
20 | Bounce duration of contact closing | ≤2 | |||||||
21 | Average breaking speed (instant breaking 6mm) |
m/s
|
1.1±0.2 | ||||||
22 | Average making speed | 0.8±0.2 | |||||||
23 | Making time |
ms
|
≤100 | ||||||
24 | Breaking time | ≤50 | |||||||
25 |
Resistance of each phase main circuit |
μ Ω |
630A | ≤50 | |||||
1250A | ≤45 | ||||||||
1600A~2000A | ≤35 | ||||||||
≥2500A | ≤25 | ||||||||
26 | Contact breaking bounce amplitude | mm | ≤2 | ||||||
27 |
Rated operating voltage | Rated operating voltage(V)AC/DC |
V |
24* | 110 | 220 | |||
Scope of normal operation voltage | Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed | ||||||||
28 | Rated voltage of energy storage motor | V | AC110/220,DC110/220 | ||||||
29 | Energy storage time | S | ≤15 |