Home ProductsGas Insulated Switchgear

IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Certification
China Knkong Electric Co.,Ltd certification
China Knkong Electric Co.,Ltd certification
I'm Online Chat Now

IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear
IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Large Image :  IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Product Details:
Place of Origin: China
Brand Name: Knkong
Certification: IEC ISO GB
Model Number: SF6 GIS HXGN-40.5
Payment & Shipping Terms:
Minimum Order Quantity: 1
Packaging Details: Standard export packaging
Delivery Time: 30 days
Payment Terms: L/C, T/T
Supply Ability: 100 Unit per month

IEC Fully Insulated 36KV 1250A RMU SF6 GIS Switchgear

Description
Rating Voltage: 36KV Rating Current: Max 1250A
Rating Frequency: 50/60Hz Standards: GB ISO IEC
OEM/ODM: Please Your CDA Drawings Type: Fully Insulated
High Light:

1250A SF6 GIS Switchgear

,

36KV SF6 GIS Switchgear

,

Fully Insulated SF6 GIS Switchgear

Fully insulated HXGN-40.5kv SF6 RMU GIS GB ISO IEC Max 1250A

 

GB ISO 36KV Gas Fully Insulated Switchgear Medium Voltage Ring Main Unit

Product Introduction

 

General

The cable switch so-called C-unit is equipped with a double-position load switch and an independent earthing switch.
The load switch uses SF6 as its arc extinguishing medium, when the load switch at open position it meets the corresponding
requirements of the isolation switch.

 

Service environment

  • Air temperature: -35℃~+40℃
  • Humidity: Monthly average 95%; Daily average 90%.
  • Altitude:≤ 1000m (Up to 5000 m can be custom)
  • Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
  • No frequent violent shake

Technical Data

No. Item Unit Parameter
1 Rated voltage kV 12 24 36
2 Rated frequency Hz 50/60
3 Rated current A 630(1250*)
4

1min Power frequency

withstand voltage

wet kV 38 50 70
dry kV 48 60 85
5 Lightning impulse withstand voltage kV 75 125/150 170
6 Rated short circuit breaking current (peak) kA 80 63 63
7 Rated active load and close circuit breaking current A 63 50 50
8 Rated transferring current A 1700 1200 1200
9 Rated short circuit making a current (peak) kA 80 63 63
10 Rated cable(line) charging breaking current A

50 and 10

50/10

11 Cable charge breaking current in earthing fault A 20 20 20
12 Rated withstand current (peak) kA 80 63 63
13 Short-time withstand current (2s) kA 25 20 20
14 Mechanism life times 5000 2000 2000

Note: For short circuit breaking and the peak current is based on Fuse plus combination

 

 