Product Details:
|
Voltage: | 40.5KV | Current: | 630A 1250A 2500A |
---|---|---|---|
Frequency: | 50Hz | Standards: | CCC,ISO9001,CE, CB,IEC60898 |
OEM/ODM: | Inquiry By Email | Manufactory: | KNKONG |
High Light: | 40.5KV high voltage vacuum circuit breaker,indoor vacuum circuit breaker,high voltage VCB |
Product Introduction
Normal service condition
Altitude |
≤1000m |
|
Ambient temperature |
Max |
+40℃ |
Min |
-15℃ |
|
Ambient humidity: Maximum average humidity |
24 hour ≤95% |
|
1 month ≤90% |
||
Maximum water vapor pressure |
24 hours ≤2.2kpa |
|
1 month ≤1.8kpa |
The ambient air has no obvious pollution of dust smoke, corrosive or combustible gases, steams or smog
VS1-40.5/E Technical Parameters
No. |
Item |
Unit |
Parameter |
1 |
Rated voltage |
KV |
40.5 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated power frequency withstand voltage/1 min |
KV |
95 |
4 |
Rated lighting impulse withstand voltage |
KV |
185 |
5 |
Rated current |
A |
630 1250 1600 2000 2500 |
6 |
Rated short-circuit breaking current |
KA |
20 25 31.5 |
7 |
Rated short-time withstand current |
KA |
20 25 31.5 |
8 |
Rated short-circuit marking current |
KA |
5063 80 |
9 |
Rated peak value of withstand current |
KA |
5063 80 |
10 |
Rated duration of short-circuit |
s |
4 |
11 |
Rated operating sequence |
O-0.3s-CO-180s-CO |
|
General Description:
VS1-40.5/T type indoor high voltage vacuum circuit breaker is used for switchgear KYN61-40.5(Z). It’s the newest type of power supply and distribution equipment. This product is in accordance with GB1984-2003 standard.
Technical Characteristics:
The design of this kind of VS1-40.5/T takes into account the Chinese market and special areas requirements, making the vacuum interrupter and conductive circuits into an embedded pole by the advantage of the solid insulation and advanced technology of APG.
This not only simplifies the pole assembly process and prevent the vacuum interrupter circuit conductive connecting bolt to run the VS1 ratio as a result of loose, but also improve reliability and avoid the effect of external mechanical force and ambient conditions (such as dust, humidity, nasty, high sea level, animal), and avoid the potential risk of vacuum interrupter operating in adverse environments caused by insulation and then lead to a lower level of the vacuum circuit breaker in the sub-gate under vacuum interrupter surface elastomer. Therefore, within the service life of the circuit breaker, the pole is completely maintenance-free. The circuit breaker’s solid insulation replaces SF6 to meet the need for external insulation. It’ s more environmental protection and represents the advanced level of the vacuum circuit breaker in the modern world.
Contact Person: Ken Chan (English)
Tel: 0086 13938551009