Product Details:
|
Voltage: | 12KV | Current: | 630-2000A |
---|---|---|---|
Breaking Current: | 20-25KA | Type: | Fixed |
Phase Spacing: | 205-310 | Brand: | KNKONG |
High Light: | 25KA Fixed Circuit Breaker,205 Phase Spacing Circuit Breaker,12KV Fixed Circuit Breaker |
205 Phase Spacing 25KA breaking Fixed Circuit Breaker
Voltage: 12KV
Current: 630-2000A
Breaking current: 20KA
Type: Fixed
Phase spacing: 205-310
Product overview
VS1-Series circuit breaker is independently developed by Knkong based on the advanced design concept; it adopts a modularized mechanism, which is easy for installation, maintenance, testing, and operation. As compared with conventional VS1 circuit breaker. it features higher operation stability, higher safety, and extended service life. The product can satisfy customer's demand for application in 12kv and 24kV power transmission and distribution systems, which is extensively applied in such industries as power, energy, petrochemical engineering, metallurgy, manufacture, traffic, building, and environmental protection as well as large-scale enterprises and national key projects.
VS1-Series circuit breaker features high stability and high reliability
In terms of mechanisms, VS1-Series vacuum circuit breakers are given special optimization to transmission parts. Modular spring mechanisms have such advantages as convenient maintenance, short power-off maintenance, high versatility of parts, and boast better compatibility with vacuum interrupters which greatly improves the technical parameters and delivers more excellent performance.
Normal service condition
Altitude | ≤1000m | |
Ambient temperature | Max | +40℃ |
Min | -15℃ | |
Ambient humidity: Maximum average humidity |
24 hours ≤95% | |
1 month ≤90% | ||
Maximum water vapor pressure | 24 hours ≤2.2kpa | |
1 month ≤1.8kpa |
Solar radiation is negligible. Vibration from the outside of switchgear and control gears is negligible. The ambient air has no obvious pollution of dust smoke, corrosive or combustible gases, steams or smog
Special service condition
Special operating conditions are to be agreed on by the manufacturer and user the manufacturer must be consulted in advance about each special operating condition:
Site altitude over 1000m
- Allow for the reduction in the dielectric strength of the air
- Or plateau type circuit breaker should be ordered, which shall meet
corresponding insulation requirements.
Increased ambient temperature
- Current carrying capacity is reduced
- Provide additional ventilation for heat dissipation
Other considerations should be consulted with the manufacturer according to Section 2.2 in IEC 62271-1
VS1-Series circuit breaker features high stability and high reliability
In terms of mechanisms, VS1-Series vacuum circuit breakers are given special optimization to transmission parts. Modular spring mechanisms have such advantages as convenient maintenance, short power-off maintenance, high versatility of parts, and boast better compatibility with vacuum interrupters which greatly improves the technical parameters and delivers more excellent performance.
Technical Parameters
No. | Item | Unit | Parameter | ||||||
1 | Rated voltage | KV | 12 | ||||||
2 | Rated frequency | Hz | 50/60 | ||||||
3 |
Rated insulation level |
1min power frequency withstand voltage(r. m. s) |
KV |
42(phase-to-phase, phase-to-earth) 48(across the isolating distance) |
|||||
Lighting impulse withstand voltage (peak) |
75(phase-to-phase, phase-to-earth) 85(across the isolating distance) |
||||||||
4 |
Rated current |
A |
630 | 630 | 1250 | 1600 | |||
1250 | 1250 | 1600 | 2000 | ||||||
2000 | 2500 | ||||||||
2500 | 3150 | ||||||||
4000 | |||||||||
5 | Rated short-circuit breaking current |
KA |
20 | 25 | 31.5 | 40 | |||
6 | Rated short-time withstand current | 20 | 25 | 31.5 | 40 | ||||
7 | Rated short-circuit marking current | 50 | 63 | 80 | 100 | ||||
8 | Rated peak withstand current | 50 | 63 | 80 | 100 | ||||
9 | Rated duration of short-circuit | s | 4 | ||||||
10 | Rated operating sequence | O-0.3s-O/C-180s-O/C | |||||||
11 | Breaking times of rated short-circuit current | Times | 30/20 times(40KA) | ||||||
12 | Mechanical endurance | Ops | 20000 | ||||||
13 | Rated single capacitor bank breaking current |
A |
630 | ||||||
14 | Rated back-to-back capacitor bank breaking current | 400 | |||||||
15 | Double-earth fault breaking current | 27.4 | |||||||
16 | Allowable maximum contact erosion |
mm |
3 | ||||||
17 | Clearance between open contacts | 10±1 | |||||||
18 | Over stroke | 3.5±0.5 | |||||||
19 | Non-simultaneity of 3-phase opening and closing |
ms
|
≤2 | ||||||
20 | Bounce duration of contact closing | ≤2 | |||||||
21 | Average breaking speed (instant breaking 6mm) |
m/s
|
1.1±0.2 | ||||||
22 | Average making speed | 0.8±0.2 | |||||||
23 | Making time |
ms
|
≤100 | ||||||
24 | Breaking time | ≤50 | |||||||
25 |
Resistance of each phase main circuit |
μ Ω |
630A | ≤50 | |||||
1250A | ≤45 | ||||||||
1600A~2000A | ≤35 | ||||||||
≥2500A | ≤25 | ||||||||
26 | Contact breaking bounce amplitude | mm | ≤2 | ||||||
27 |
Rated operating voltage | Rated operating voltage(V)AC/DC |
V |
24* | 110 | 220 | |||
Scope of normal operation voltage | Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed | ||||||||
28 | Rated voltage of energy storage motor | V | AC110/220, DC110/220 | ||||||
29 | Energy storage time | S | ≤15 |