20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type

Certification
China Knkong Electric Co.,Ltd certification
China Knkong Electric Co.,Ltd certification
I'm Online Chat Now

20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type

20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type
20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type

Large Image :  20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type

Product Details:
Place of Origin: China
Brand Name: KNKONG
Certification: CB,ISO,IEC
Model Number: VS1-12
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: USD 1000-2000 Each
Packaging Details: Standard export packaging
Delivery Time: 15 working days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 1000 Unit per month

20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type

Description
Voltage: 12KV Current: 2000A
Breaking Current: 20-25KA Type: Fixed
Standard: GB,IEC,ISO Manufactory: KNKONG
High Light:

20KA Breaking VCB Circuit Breaker

,

IEC Indoor Switchgear VCB Circuit Breaker

,

2000A Fixed Circuit Breaker

12KV 2000A fixed type indoor VCB 205 phase spacing VS1-12

Voltage: 12KV

Current: 2000A

Breaking current: 20KA

Type: Fixed

Phase spacing: 205

 

Product overview

The vacuum circuit breaker is suitable for 12kV, three-phase AC 50Hz indoor switchgear, and can be used as a protection and control unit for substation equipment in industrial and mining enterprises. The spring operating mechanism of VS1 series circuit breaker adopts modular and independent frame design, which can be operated with KYN28-12(24) central and fixed switchgear. These circuit breakers can be fixedly installed or assembled with a truck as a trolley unit

 

VS1-Series circuit breakers are Class M2.c2 and E2 model

Vs1-Series circuit breaker is available for the environment. Maintenance-free and capable of frequent operation. Compared with traditional circuit breaker products. These breakers have their mechanical endurance raised to 20 000 ops from 10, 000 ops with an enormous improvement. The type test for capacitive current breaking shows an extraordinarily low restrike probability. These products feature prolonged electrical endurance and free maintenance.

 

Technical Parameters

No. Item Unit Parameter
1 Rated voltage KV 12
2 Rated frequency Hz 50/60
3

 

Rated insulation level

1min power frequency withstand voltage(r. m. s)

 

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)

 

 

4

 

 

Rated current

 

 

A

630 630 1250 1600
1250 1250 1600 2000
    2000 2500
    2500 3150
      4000
5 Rated short-circuit breaking current

 

KA

20 25 31.5 40
6 Rated short-time withstand current 20 25 31.5 40
7 Rated short-circuit marking current 50 63 80 100
8 Rated peak withstand current 50 63 80 100
9 Rated duration of short-circuit     s 4
10 Rated operating sequence   O-0.3s-O/C-180s-O/C
11 Breaking times of rated short-circuit current Times 30/20 times(40KA)
12 Mechanical endurance Ops 20000
13 Rated single capacitor bank breaking current

 

A

630
14 Rated back-to-back capacitor bank breaking current 400
15 Double-earth fault breaking current 27.4
16 Allowable maximum contact erosion

 

mm

3
17 Clearance between open contacts 10±1
18 Over stroke 3.5±0.5
19 Non-simultaneity of 3-phase opening and closing

ms

 

≤2
20 Bounce duration of contact closing ≤2
21 Average breaking speed (instant breaking 6mm)

m/s

 

1.1±0.2
22 Average making speed 0.8±0.2
23 Making time

ms

 

≤100
24 Breaking time ≤50

 

 

25

 

Resistance of each phase main circuit

 

μ Ω

630A ≤50
1250A ≤45
1600A~2000A ≤35
≥2500A ≤25
26 Contact breaking bounce amplitude mm ≤2

 

27

Rated operating voltage Rated operating voltage(V)AC/DC

 

V

24* 110 220
Scope of normal operation voltage Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28 Rated voltage of energy storage motor V AC110/220,DC110/220
29 Energy storage time S ≤15

 

20KA Breaking Indoor Switchgear VCB Circuit Breaker Fixed Type 0

 

 