Home ProductsVCB Circuit Breaker

Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker

Certification
China Knkong Electric Co.,Ltd certification
China Knkong Electric Co.,Ltd certification
I'm Online Chat Now

Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker

Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker
Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker

Large Image :  Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker

Product Details:
Place of Origin: China
Brand Name: Knkong
Certification: CCC,ISO9001,CE, CB,IEC60898
Model Number: VS1-40.5/E
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: USD 1000-3000
Packaging Details: Standard export packaging
Delivery Time: 30 days
Payment Terms: L/C, T/T
Supply Ability: 100 Unit per month

Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker

Description
Rating Voltage: 40.5 KV Rating Current: 630/1250/1600/2000/2500A
Rating Frequency: 50Hz Standerds: CCC,ISO9001,CE, CB,IEC60898
OEM/ODM: Available
High Light:

20KA Indoor VCB

,

Indoor VCB Circuit Breaker

,

20KA VCB Circuit Breaker

Indoor VCB Sleeve or Embedded pole 12-40.5KV,three-phase 50HZ 400/630A, AC/DC 110/220V CCC,ISO9001,CE, CB,IEC60898

 

Product Introduction

 

Structure Features

1. Reliable modular spring operating mechanism: the layout of the spring operating mechanism is up-down style, which has the function of manual storing energy and electric storing energy; Small size, good overall stiffness, and performance

 

2. Sleeve structure(VS1-40.5): The vacuum extinguishing chamber of the main circuit is inside the closed insulating drum; The material of the insulating drum is epoxy resin which has reliable mechanical and electrical properties. Using advanced APG process molding, the insulating drum has the role of support and interphase and relative insulation effect

 

3. Encapsulated pole structure(VS1-40.5E): The conductive circuit adopts solid encapsulation pole; Using advanced APG process molding, put the vacuum interrupter and other parts (for primary circuit ) solid encapsulated with epoxy material, make the main circuit module. With inside and outside double skirt design, the pole has features such as large creepage distance, high mechanical strength, high part accuracy, fewer parts, no secondary adjustments, and a small lapped surface

 

4. Standard on-off function module: Modular design spring mechanism, which includes two functional modules: closing and opening; It has the characteristics of convenient maintenance, quick replacement, and short maintenance time; No readjustment for the entire circuit breaker’s operating mechanism after replacing the closing and breaking module, which can reduce maintenance work

 

5. Better handcart interchangeability and adaptability, installation size and ZN85, VD4, and other products; Strong breaking ability, long service life

 

Normal service condition

Altitude ≤1000m
Ambient temperature Max +40℃
Min -15℃

Ambient humidity:

Maximum average humidity

24 hour ≤95%
1 month ≤90%
Maximum water vapor pressure 24 hours ≤2.2kpa
1 month ≤1.8kpa

The ambient air has no obvious pollution of dust smoke, corrosive or combustible gases, steams or smog

 

VS1-40.5/E Technical Parameters

No. Item Unit Parameter
1 Rated voltage KV 40.5
2 Rated frequency Hz 50
3 Rated power frequency withstand voltage/1 min KV 95
4 Rated lightning impulse withstand voltage KV 185
5 Rated current A 630 1250 1600 2000 2500
6 Rated short-circuit breaking current KA 20 25 31.5
7 Rated short-time withstand current KA 20 25 31.5
8 Rated short-circuit marking current KA 50 63 80
9 Rated peak value of withstanding current KA 50 63 80
10 Rated duration of short-circuit s 4
11 Rated operating sequence   O-0.3s-CO-180s-CO
12 Breaking time ms ≤80
13 Mechanical endurance times 10000
14 Rated single capacitor bank breaking current A 400/630
15 Rated short circuit breaking current breaking times times 30
16 Size (length*width*high) mm 1246*1700*905
17 Rated voltage of energy storage motor V AC110/220, DC110/220
18 Weight Kg 466

 

Mechanical Properties Parameters

No. Item Unit Parameter
1 Clearance between open contacts mm 18±2
2 Over stroke 3.5~4
3 Rated power of energy storage motor W 230
4 Energy storage time s ≤15
5 Bounce duration of contact closing

 

ms

≤3
6 Non-simultaneity of 3-phase opening and closing ≤2
7 Breaking time ≤70
8 Making time ≤90
9 Break-brake bounce m ≤3
10 Average breaking speed m/s 1.7±0.3
11 Average making speed 0.7±0.3

 

Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker 0Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker 1Sleeve / Embedded Pole 20KA Indoor VCB Circuit Breaker 2