Home ProductsVCB Circuit Breaker

Indoor 20KA Breaking Switchgear Circuit Breaker Fixed Type VS1 Series

Certification
China Knkong Electric Co.,Ltd certification
China Knkong Electric Co.,Ltd certification
I'm Online Chat Now

Indoor 20KA Breaking Switchgear Circuit Breaker Fixed Type VS1 Series

Indoor 20KA Breaking Switchgear Circuit Breaker Fixed Type VS1 Series
Indoor 20KA Breaking Switchgear Circuit Breaker Fixed Type VS1 Series

Large Image :  Indoor 20KA Breaking Switchgear Circuit Breaker Fixed Type VS1 Series

Product Details:
Place of Origin: China
Brand Name: KNKONG
Certification: CB,ISO,IEC
Model Number: VS1-12
Payment & Shipping Terms:
Minimum Order Quantity: 1
Packaging Details: Standard export packaging
Delivery Time: 15 working days
Payment Terms: L/C, T/T, Western Union
Supply Ability: 1000 Unit per month

Indoor 20KA Breaking Switchgear Circuit Breaker Fixed Type VS1 Series

Description
Runing Voltage: Regular 12KV Runing Current: Max 2000A
Breaking Current: 20-25KA Type: Fixed
Standard: GB,IEC,ISO Manufactory: KNKONG-ELECTRIC
High Light:

20KA Breaking Switchgear Circuit Breaker

,

Indoor Switchgear Circuit Breaker

,

Fixed Type Switchgear Circuit Breaker

20KA Breaking indoor type switchgear using vacuum circuit breaker fixed type VS1 series

Voltage: regular 12KV

Current: max 2000A

Breaking current: 20KA

Type: Fixed

Phase spacing: 205

 

Product overview

VS1 vacuum circuit breaker is used in 12kV, 24KV three-phase AC 50/60Hz indoor switchgear, and can be used for the protection and control of industrial and mining enterprises and substation equipment. The spring operating mechanism of VS1 series circuit breaker is a modular independent frame design, installed in KYN28-12 (24) centralized and fixed switch cabinets. The VS1 circuit breaker can be fixedly installed or used in combination with a trolley.

 

VS1-Series circuit breakers are Class M2.c2 and E2 model

VS1 series circuit breakers are maintenance-free and can be operated frequently. Compared with traditional circuit breaker products, the mechanical durability of VS1 circuit breaker has been improved from 10,000 ops to 20,000 ops, which is a huge improvement. The type test of capacitive current interruption shows a very low probability of re-arcing. VS1 has a long electrical life and free maintenance.

 

Technical Parameters

No. Item Unit Parameter
1 Rated voltage KV 12
2 Rated frequency Hz 50/60
3

 

Rated insulation level

1min power frequency withstand voltage(r. m. s)

 

KV

42(phase-to-phase, phase-to-earth)

48(across the isolating distance)

Lighting impulse withstand voltage (peak)

75(phase-to-phase, phase-to-earth)

85(across the isolating distance)

 

 

4

 

 

Rated current

 

 

A

630 630 1250 1600
1250 1250 1600 2000
    2000 2500
    2500 3150
      4000
5 Rated short-circuit breaking current

 

KA

20 25 31.5 40
6 Rated short-time withstand current 20 25 31.5 40
7 Rated short-circuit marking current 50 63 80 100
8 Rated peak withstand current 50 63 80 100
9 Rated duration of short-circuit     s 4
10 Rated operating sequence   O-0.3s-O/C-180s-O/C
11 Breaking times of rated short-circuit current Times 30/20 times(40KA)
12 Mechanical endurance Ops 20000
13 Rated single capacitor bank breaking current

 

A

630
14 Rated back-to-back capacitor bank breaking current 400
15 Double-earth fault breaking current 27.4
16 Allowable maximum contact erosion

 

mm

3
17 Clearance between open contacts 10±1
18 Over stroke 3.5±0.5
19 Non-simultaneity of 3-phase opening and closing

ms

 

≤2
20 Bounce duration of contact closing ≤2
21 Average breaking speed (instant breaking 6mm)

m/s

 

1.1±0.2
22 Average making speed 0.8±0.2
23 Making time

ms

 

≤100
24 Breaking time ≤50

 

 

25

 

Resistance of each phase main circuit

 

μ Ω

630A ≤50
1250A ≤45
1600A~2000A ≤35
≥2500A ≤25
26 Contact breaking bounce amplitude mm ≤2

 

27

Rated operating voltage Rated operating voltage(V)AC/DC

 

V

24* 110 220
Scope of normal operation voltage Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
28 Rated voltage of energy storage motor V AC110/220,DC110/220
29 Energy storage time S ≤15

 