Product Details:
|
Voltage: | 12KV-24KV | Current: | 630A |
---|---|---|---|
Breaking Current: | 20-25KA | Type: | Fixed Type |
Phase Spacing: | 310mm | Manufactory: | KNKONG-ELECTRIC |
High Light: | IEC Fixed Type VCB Circuit Breaker,24KV Modularized VCB Circuit Breaker,310mm Phase Spacing VCB Circuit Breaker |
310mm Phase spacing fixed type12-24KV modularized vacuum circuit breaker
Voltage: 12-24KV
Current: 630-2000A
Breaking current: 20KA
Type: Fixed
Phase spacing: 310mm
Product overview
VS1-Series circuit breaker features high stability and high reliability
The operating mechanism of Knkong-electric's VS1 series vacuum circuit breaker is specially optimized for transmission components. The modular spring mechanism makes maintenance more convenient, the maintenance time after power failure is greatly shortened, and the parts are universal. At the same time, the vacuum interrupter has good compatibility and greatly improved performance.
Technical Parameters
No. | Item | Unit | Parameter | ||||||
1 | Rated voltage | KV | 12 | ||||||
2 | Rated frequency | Hz | 50/60 | ||||||
3 |
Rated insulation level |
1min power frequency withstand voltage(r. m. s) |
KV |
42(phase-to-phase, phase-to-earth) 48(across the isolating distance) |
|||||
Lighting impulse withstand voltage (peak) |
75(phase-to-phase, phase-to-earth) 85(across the isolating distance) |
||||||||
4 |
Rated current |
A |
630 | 630 | 1250 | 1600 | |||
1250 | 1250 | 1600 | 2000 | ||||||
2000 | 2500 | ||||||||
2500 | 3150 | ||||||||
4000 | |||||||||
5 | Rated short-circuit breaking current |
KA |
20 | 25 | 31.5 | 40 | |||
6 | Rated short-time withstand current | 20 | 25 | 31.5 | 40 | ||||
7 | Rated short-circuit marking current | 50 | 63 | 80 | 100 | ||||
8 | Rated peak withstand current | 50 | 63 | 80 | 100 | ||||
9 | Rated duration of short-circuit | s | 4 | ||||||
10 | Rated operating sequence | O-0.3s-O/C-180s-O/C | |||||||
11 | Breaking times of rated short-circuit current | Times | 30/20 times(40KA) | ||||||
12 | Mechanical endurance | Ops | 20000 | ||||||
13 | Rated single capacitor bank breaking current |
A |
630 | ||||||
14 | Rated back-to-back capacitor bank breaking current | 400 | |||||||
15 | Double-earth fault breaking current | 27.4 | |||||||
16 | Allowable maximum contact erosion |
mm |
3 | ||||||
17 | Clearance between open contacts | 10±1 | |||||||
18 | Over stroke | 3.5±0.5 | |||||||
19 | Non-simultaneity of 3-phase opening and closing |
ms
|
≤2 | ||||||
20 | Bounce duration of contact closing | ≤2 | |||||||
21 | Average breaking speed (instant breaking 6mm) |
m/s
|
1.1±0.2 | ||||||
22 | Average making speed | 0.8±0.2 | |||||||
23 | Making time |
ms
|
≤100 | ||||||
24 | Breaking time | ≤50 | |||||||
25 |
Resistance of each phase main circuit |
μ Ω |
630A | ≤50 | |||||
1250A | ≤45 | ||||||||
1600A~2000A | ≤35 | ||||||||
≥2500A | ≤25 | ||||||||
26 | Contact breaking bounce amplitude | mm | ≤2 | ||||||
27 |
Rated operating voltage | Rated operating voltage(V)AC/DC |
V |
24* | 110 | 220 | |||
Scope of normal operation voltage | Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed | ||||||||
28 | Rated voltage of energy storage motor | V | AC110/220,DC110/220 | ||||||
29 | Energy storage time | S | ≤15 |