Home ProductsMetal Clad Switchgear

AIS Electrical LV Panel 6KV Indoor Switchgear

Certification
China Knkong Electric Co.,Ltd certification
China Knkong Electric Co.,Ltd certification
I'm Online Chat Now

AIS Electrical LV Panel 6KV Indoor Switchgear

AIS Electrical LV Panel 6KV Indoor Switchgear
AIS Electrical LV Panel 6KV Indoor Switchgear

Large Image :  AIS Electrical LV Panel 6KV Indoor Switchgear

Product Details:
Place of Origin: China
Brand Name: KNKONG
Certification: ISO IEC GB
Model Number: KYN28
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: USD 10000-20000 Each
Packaging Details: Standard export packaging
Delivery Time: 15 working days
Payment Terms: L/C, T/T
Supply Ability: 500 unit per month

AIS Electrical LV Panel 6KV Indoor Switchgear

Description
Voltage: 6KV Current: From 630A To 2000A
Frequency: 50Hz / 60Hz OEM/ODM: Available
Manufactory: KNKONG Type: AIS
High Light:

Electrical LV Panel 6KV

,

6KV Indoor Switchgear

,

AIS Electrical LV Panel

Switchgear 11KV switchgear metal clad power switchgear MV switchgear panel

11KV switchgear metal clad power switchgear MV switchgear panel

KYN28 metal-enclosed switchgear,
Knkong,ABB or Schneider inside
3.6-24KV, three-phase, AC 50/60Hz
Can be equipped with VS1 VD4 3AH5 ZN65A VB2 VCB
Meets IEC standard
Send us your SLD (Single Line Drawing) or requirements to get the price
Inquire

Product Introduction

General

KYN28A-12 metal armored central removable switchgear is a complete set of power distribution equipment for three-phase AC 50Hz, rated voltage 3.6-12kV single bus and single bus section system. It is mainly used in power plants, substations, transformation and distribution centers of industrial and mining enterprises, and large high-voltage motor starting equipment, etc., for receiving and distributing electric energy, and for controlling, protecting and monitoring circuits.

 

Using environment
No obvious pollution by dust, smoke, corrosive and/or flammable gas, steam, or salt spray;

Pollution level: level Ⅱ;
A place without severe vibration;
The amplitude of electromagnetic interference induced in the secondary system is less than 1.6kV;
Special environment: When the above allowable use environment conditions are exceeded, please consult with the manufacturer for ordering.

 

Technical data

No. Item Unit Parameter
1 Rating voltage kV 3.6~24
2 Rating frequency Hz 50/60
3 Rating current

 

 

 

A

630,1250,1600,2000,2500,3150,4000

 

4

Branch busbar Rated current  

 

630,1250,1600,2000,2500,3150,4000

 

5

Main busbar Rated current  

 

630,1250,1600,2000,2500,3150,4000

 

 

6

1min Power frequency withstand voltage wet

 

 

KV

38 50/60
   

 

dry

 

 

48

 

60/65

 

7

Lightning impulse withstand voltage

 

kV

 

75

 

95/125

 

8

Rated short circuit breaking current (peak)

 

 

KA

 

40/50/63/80/100

 

9

Short time withstand current(4s)  

 

20/25/31.5/40

10 Protection type   IP4X for housing

 

AIS Electrical LV Panel 6KV Indoor Switchgear 0AIS Electrical LV Panel 6KV Indoor Switchgear 1